© 2008 by the Rector and Visitors of the University of Virginia.

The information contained on the University of Virginia’s Department of Information Technology and Communication (ITC) website is provided as a public service with the understanding that ITC makes no representations or warranties, either expressed or implied, concerning the accuracy, completeness, reliability or suitability of the information, including warrantees of title, non-infringement of copyright or patent rights of others. These pages are expected to represent the University of Virginia community and the State of Virginia in a professional manner in accordance with the University of Virginia’s Computing Policies.

Standards for Building Telecommunications Facilities

University of Virginia

Standards for Building Telecommunications Facilities

September 2005[1]

Introduction

This document establishes standards for the installation of telecommunications facilities in University buildings and supersedes “Recommendations for Telecommunications Wiring Guidelines” issued by the Data Communications Working Group July 11, 1990.  While the standards are meant to apply particularly to new construction and major renovation projects, they should also be followed when wiring or rewiring existing buildings whenever it is practical and economically feasible.  Information Technology & Communication will act as telecommunications consultant and review the plans for all university construction and renovation projects.  In buildings where Health System Computing Services (HS/CS) or Health Services Foundation operate networks, these departments will also act as consultants and review telecommunications plans.

 

It is recognized that the design process and the allocation of space in all construction and renovation projects is actually a negotiation between all interested parties.  These standards provide information for the initial project design.  Once the initial phase is complete, ITC and the other consultants will work with the building committee to perform the detailed work and ensure that a modern network infrastructure can be installed.  ITC and the other reviewers will always be flexible and make sure that the needs of the building occupants are met at the minimum possible cost.

 

Reference material used in preparing this document includes the “ElA/TIA[2] Building Telecommunications Wiring Standards”.  The standards referred to here are published in six different documents[3], all containing related information from which a complete commercial or residential building wiring system is defined.  The University standards take precedence over all others.

 

 



Table of Contents

 

Introduction                                                                                                                           1

Telecommunications Closet Specifications                                                      3

Horizontal Wiring Pathways                                                                                        5

Building Entrance Termination Space                                                                   7

Horizontal Wiring Components                                                                                  8

Building Backbone Cabling                                                                                           9

Miscellaneous Topics                                                                                                     10

Appendix: Fiber Specifications                                                                                  11

Appendix: Station Cable Specifications                                                              12

Appendix: Wallplate and Outlet Diagrams                                                       14

Appendix: EIA/TIA Standards Publications                                                         15

 

 



Telecommunications Closet Specifications

 

1.      General
Telecommunications closets house the wiring and electronic equipment that are used to connect user workstations to the University communications network. These closets are designed for and intended for the intra-building distribution of centrally managed telephone, data communications, and video services and in no instance shall they be used to support other building utilities.
Telecommunications closets must be located so they can be accessed from hallways.

 

2.      Dimensions
Closets serving up to 100 outlet locations shall be 6x8 ft. minimum. In areas where greater than 100 outlet locations are anticipated the closet shall be sized on a case-by-case basis. Ceilings shall be 9 ft. minimum in height; no false ceilings will be allowed. The door shall be a minimum of 36” wide and 80” high, open outward, and be fitted with a keyed lock. Lock keying should meet ITC and/or HS/CS specifications as appropriate.  A magnetic card system may be requested in some cases in order to meet a particular requirement.

 

3.      Interior Furnishings
Floors, walls, and ceilings shall be treated to minimize dust.  Paint or other surface finishes shall be of a texture and color such that room lighting is enhanced.  Three walls shall be fitted floor to ceiling with BC grade ¾” fire rated plywood.

 

4.      Lighting
Lighting shall be a minimum of 50-foot candles measured 3 feet above the finished floor, mounted 8.5 ft. above the finished floor. No wall-mounted lighting will be allowed.

 

5.      AC Power
A minimum of two (2) dedicated 20 amp, 120 volt circuits and one (1) dedicated 30 amp 208/220 volt circuit, outlet NEMA size L14-30-R30A 125/250V shall be provided. Quad service outlets shall be placed at four (4) ft. intervals along the length of the four walls and 18 inches above the finished floor. Service panel location and breaker positions shall be clearly marked. Access shall be available to the main building-grounding electrode.  Power for communications wiring closets should always be supplied from building emergency power systems whenever emergency power is available in a building.  Some wiring closets in some buildings will need additional electrical power depending on special needs.  These extra needs will be specified by ITC and/or HS/CS during the review process.

 

6.      Environment
Temperature and humidity control shall be continuous over the range 50 to 85 degrees F with 30% to 75% relative humidity non-condensing. The cooling system should maintain the ambient room temperature of below 75 degrees F.  A positive pressure shall be maintained with an air exchange sufficient to dissipate the heat generated by electronic/electrical equipment. Dissipated power will typically be less than 6,000 watts.  The cooling system for the wiring closet must operate on a 24x7 basis, 365 days per year.  Wiring closet cooling can not be controlled by energy management systems that cut off cooling when the building is not occupied.  When additional power is specified per Section 5 above, a corresponding increase in cooling capacity is required.


7.      Closet Penetrations
Floor penetrations for vertically stacked closets shall be a minimum of two 4” penetrations per closet.  Each penetration will include a bushed sleeve extending 1” above the finished floor. It is recommended that all penetrations be in clusters at a location in the closet stack specified by ITC and/or HS/CS. Penetrations for horizontal conduit or cable tray runs which use ceiling pathways should be near the 8 ft. level.  Additional penetrations may be needed depending on the density of network devices needed in a particular area.

 

8.      Closet Linkage
When multiple closets exist on a single floor, these closets must be interconnected via horizontal cable pathways.  If drop ceilings are used, the closets should be interconnected using cable ladder that is 12 inches wide and 4 inches deep.  In locations without drop ceilings a minimum of two four (4) inch conduits should be provided to implement the closet interconnection.  A conduit system must include pull boxes at 100 foot intervals and after every pair of 90° bends. Conduits entering the closet through a 90 degree bend, whether from floor or ceiling, shall do so with a bend radius of 18 inches for 2’ Inner Diameter (ID) or less. Conduits with greater than a 2” ID shall have a radius ten times conduit ID. Pull cords shall be provided in all conduits. 

 

9.      Closet-to-Wall Outlet Distance
The closet-to-wall outlet distance shall be a maximum of 290 cable-feet. Multiple closets shall be provided where necessary to meet this requirement.  Remember to include the vertical components of a cable path when calculating distances.  The 290 foot limit is cable length and not simply floor path length.

 

10.  Number of closets per building
General rule of thumb is one communications closet per 10,000 square ft of office space.

11.  Fire Suppression
Wiring closets should not include fire sprinkler heads.  If sprinkler heads must be accommodated, a dry-pipe system is preferred.

 

 


Horizontal Wiring Pathways

 

1.        General
The term “horizontal wiring” refers to a number of cable types that run from a communications closet on a particular floor of a building to workstations on that floor. Where there are multiple closets on a floor, it can also include wiring-hub interconnection cables.  These interconnection cables are typically some combination of copper and fiber optic cables.  Careful design work on the horizontal cable pathways to minimize total cable length will help to lower wiring costs and in some cases might decrease the total number of wiring closets needed to serve a building.

2.        Recognized Cables
The following cable types are recognized as intra-building horizontal wiring, see appendix for details.

a)        Category 5E and Category 6 twisted-pair cables.

b)        RG-6 or equivalent coaxial cables.

c)        FDDI-grade 62.5 micron multi-mode and 8 micron single-mode optical fiber cable.

 

3.        Ceiling CablePathways
Ceilings used as distribution pathways for horizontal cabling shall meet the following conditions:

 

a)        If a fixed ceiling has to be used as a cable route, properly sized conduit must be installed as a pass through.

Conduit Capacity:

4 inch conduit = 100 Category 5 cables, (50 network drops)

3 inch conduit = 50 Category 5 cables, (25 network drops)

2 inch conduit = 24 Category 5 cables, (12 network drops)

1 inch conduit = 8 Category 5 cables, (4 network drops) 

 

b)        Ceilings of lay-in tiles which allow easy access to a suitable space above are recommended. Suitable space is defined as that which supports the installation and ready use of a 12” open-frame center spine cable ladder.  These cable ladders should be installed in all hallways.  Solid bottom cable trays are not to be used.

c)        Height of the cable ladder/raceway above the finished floor shall be no more than 11’.

d)        Metal cable ladders/raceways shall be bonded to the building ground per applicable code.

e)        Plenum ceilings add to the cost of wiring a building since special type of cable must be used to meet fire codes.

 

4.         Raceway-to-Outlet Cable Path
 A 1” conduit shall be provided from the cable raceway area above the ceiling to a quad wall box, or quad boxes if specifically requested, for each workstation location.  The quad box should be fitted with a mud ring to size it down to use a duplex outlet faceplate.  The conduit should be installed from the outlet box to the cable ladder in main corridor.  When no cable ladder exists, a simple stub termination of the in-wall outlet conduit extending several inches into the ceiling space is preferred.  A cable ladder should be installed for all addition and renovation projects.  Enclosed raceways should not be installed as this restricts access.  Pull ropes shall be installed in all conduits as part of the conduit installation work.  Daisy-chained systems that originate in the wiring closet and serve multiple outlets via a single conduit are not allowed.


Building Entrance Termination Space

1.      General
The building entrance room houses the facilities necessary to terminate the inter-building cable plant and to transition to the intra-building communications backbone cabling. Along with cable splice facilities, this room will also hold the lightening surge suppressors needed for the telephone system cable plant. The intra-building backbone cables run from this room via the vertical riser and horizontal pathways to the communications wiring closets throughout the building.  In some cases this room may also serve as a wiring closet for the lower level of the building.

 

2.      Dimensions
Rooms shall be 6x8 ft. minimum with 8 ft. ceilings. The door shall be 80” high and 36” wide minimum, open outward, and be fitted with a keyed lock.

 

3.      Interior Furnishings

     Floors, walls, and ceilings shall be treated to minimize dust. Paint or other surface finishes shall enhance room lighting. Three walls shall be fitted floor to ceiling with BC grade ¾” fire rated plywood.

 

4.      Lighting

     Lighting shall be ceiling mounted and measure 50 foot-candles three feet above the finished floor.

 

5.      AC Power          
Two dedicated 20 amp 120 volt circuits shall be provided. A minimum of one quad outlet per wall shall be provided.  Outlets should be marked with associated breaker number and location of panel. Access shall be provided to main building ground electrode.  In cases where this room also serves as a wiring closet, the additional electrical power requirements for a wiring closet must also be met.

6.      Environment
In cases where the Building Entrance room is also acts as a wiring closet, the cooling specifications for a normal wiring closet must also be met.

7.      Entrance pathway sizing
The size of the pathways, if any, between the building entrance point and the Building Entrance room shall be the same as the actual facilities that enter the building.  This is generally two 4” conduits.

 

8.      Closet Linkage
A backbone/riser cable pathway having the capacity of two (2) 4” conduits minimum shall be established between the Building Entrance Facility and one of the N vertically stacked closets configured as described in Sections 7 and 8 of the Telecommunications Closet Specification portion of this document.  If wiring closets are not stacked and positioned at random throughout a building, a 12” wide by 4” deep ladder rack shall be provided from the entrance facility to each closet.

Horizontal Wiring Components

 

1.      General
Horizontal wiring is that portion of the building telecommunications infrastructure which supports signal transmission from the telecommunications closet to the user workstation.  Included in this section are the closet-to-workstation cable, telecommunications closet termination hardware, and workstation wall outlet hardware.

 

2.      Closet-to-workstation Cable Types
Recognized horizontal cable types are Category 5E and Category 6 twisted-pair cable, RG-6 coaxial cable, 62.5 micron optical fiber, or other special cable types as specified by ITC and/or HS/CS. See appendix.

 

3.      Installed cable
Standard practice shall be to install two Category 5E twisted-pair cables from the telecommunications closet to each outlet location. Coax and/or fiber shall be installed as specified on a case-by-case basis. Horizontal pathways from closet to the workstation outlets shall be sized to accommodate all three media types; exposed wiring is not allowed.  Some locations may require three twisted-pair cables per outlet.

 

4.      Twisted-pair Closet Terminations
Twisted-pair wiring shall be terminated in the telecommunications closet using Avaya 110 Cross-Connect System. Data pair cross-connects shall use Category 5E, Category 6 components, including cordage, and be arranged such that any user workstation can access any communications hub port. See the appendix for details.

 

5.      Twisted-pair Wall Outlet Terminations
Twisted-pair wiring wall outlet terminations shall be Category 5E or Category 6 compliant Avaya RJ-45 jacks. The outlet wall plate shall be part of a modular system that supports twisted-pair, coax, and fiber. See appendix for details.  Some locations may require specialized terminations as specified by ITC and/or HS/CS.

 

6.      Communications outlet density
Standard practice shall be to install two (2) communications outlets per 100 sq. ft. of assignable office space.  In all other areas, communications outlets to be provided as required.  Interaction with the department that will occupy the space is essential when determining the number and location of telecommunications outlets.

 


Building Backbone Cabling

 

1.      General
Building backbone cabling refers to the intra-building communication trunk system. The system consists of multi-pair telephone riser cable, coaxial trunk cable, optical fiber cable, and in some cases Category 5E or Category 6 twisted pair cabling. These cables bring the various communications services from the building entrance facility to the telecommunications closets on each floor from whence they are distributed via the horizontal wiring systems to the individual user outlets.

 

2.      Topology
Building backbone cabling shall have a star topology unless otherwise specified.

 

3.      Intra-building Data Backbone
The data network backbone cable installed shall be a combination of 62.5 micron multi-mode and 8 micron single-mode optical cable. No in-building distance limitations apply.

 

4.      Intra-building Video Trunk
The building video backbone shall be ½”, 75 ohm semi-rigid coax. No distance limitations apply.

 

5.      Intra-building Telephone Riser
Telephone risers shall be unshielded twisted pair CMR rated cable. Two pairs per 100 sq. ft. of assignable space shall be provided to each floor if the exact number of telephones required is unknown. If the number of telephones required is known, allow for 100% growth.

 


Miscellaneous Topics

 

1.      General
This section contains comments on a variety of topics pertaining to building wiring that do not fit exclusively (at this time) under one of the five main headings.

2.      Documentation
Documentation shall be computer based and include both schematic and table forms. Elements of the building infrastructure to be documented shall be chosen based on local requirements and with reference to the TIA/EIA-606 infrastructure administration standard. A documentation maintenance program shall be developed and put into effect.

 

3.      Proximity to EMI sources
Telecommunications closets and wiring pathways shall not be located in close proximity to sources of electromagnetic interference. Special attention shall be given to potential EMI sources such as large electric motors, welding equipment, etc. Wiring pathways shall be at least 12” from unshielded power lines of <480 volts and at least 5” from fluorescent lighting fixtures.

 



Fiber Specifications

 

 

 

 

Intra-building Fiber Cable

All fiber shall be Corning multimode graded index fiber with a 62.5/125 micron core/cladding diameter, buffered to 900 microns, and housed in a UL, OFNR rated jacket or standard Corning SMF-28e single-mode 8 micron cable.

 

 

 

 

 

Minimum Performance Specifications for Multi-mode cable

 

Wavelength (nm)

Attenuation (dB/Km)

Capacity (MHz-Km)

850

3.75

160

1300

1.5

500

 

Approved cable: SEICOR Inc., MIC series fiber optic cable.

 

 


 

Station Cable Specifications

Wiring closet-to-workstation cable shall have four (4) twisted-pair and meet all EIA Category 5E, Category 6 specifications. 

 

 

 

Attenuation @ 100 MHz

Next Loss @ 100 MHz

Minimum Performance Specifications

67 dB/1000 ft

32 dB @ 1000 ft

 

 

 

 

 

Minimum Approved Cable Types

Cable Application

Approved Cable Model

Normal cable use

Avaya PDS LAN Cable No. 1061

Plenum-rated cable use.

Avaya PDS LAN Cable No. 2061

 

 

 

 

 

 


 

 

           


 

 

 

 

 



 

Appendix - EIA/TIA Standards Publications

 

 

 

 

 

 

EIA/TIA-568

 

Commercial Building Telecommunications Wiring Standard

 

 

TSB-36

 

Technical Systems Bulletin: Additional Cable Specifications for Unshielded Twisted-Pair Cables.

 

 

TSB-40

 

Technical Systems Bulletin: Additional Transmission Specifications for Unshielded Twisted-Pair Connecting Hardware.

 

 

EIA/TIA-569

 

Commercial Building Standard for Telecommunications Pathways and Spaces.

 

 

EIA-570

 

Residential and Light Commercial Telecommunications Wiring Standard.

 

 

EIA-606

 

The Administration Standard for the Telecommunications Infrastructure of Commercial Buildings.

 

 

 



[1] Update to the May 1993 standards approved by the University Committee on Information Technology (UCIT) with additional editing for clarity and technology in September 2005.

[2] Electronic Industries Association / Telecommunications Industry Association.

[3] See appendix.